- Choose the conduit type. Select EMT, PVC Schedule 40, PVC Schedule 80, RMC, IMC, FMC, LFMC, or LFNC. Each type has different internal dimensions for the same trade size. EMT is the most common for residential and light commercial work.
- Select the trade size. Pick the conduit trade size you plan to install or already have in place, from 1/2" through 6". If you're unsure, start with 3/4" for residential branch circuits or 1" for larger runs.
- Set the run type. Choose "Standard run" for most installations. Select "Nipple (24 in or less)" only for short conduit stubs between boxes or panels, which allow a higher 60% fill.
- Pick the insulation type. THHN/THWN-2 is the most common conductor insulation for building wiring. Choose XHHW-2 for larger feeders, USE-2/RHH/RHW-2 for service entrance conductors, or PV Wire for solar runs. Use "Custom diameter" if you have a cable with a known outside diameter.
- Select the conductor size and quantity. Choose the wire gauge (14 AWG through 1000 kcmil) and enter how many conductors of that size you plan to pull. For a typical 20 amp branch circuit, that's four 12 AWG THHN (two hots, neutral, ground or two circuits sharing a neutral).
- Click "Calculate conduit fill" to see the fill percentage, pass or fail status, remaining capacity, and a next size suggestion if the fill exceeds the limit.
Pro tip: Leave 10% to 15% spare capacity when the raceway run has more than two 90 degree bends or exceeds 100 feet. A conduit fill percentage that passes NEC limits can still make pulling wire difficult in long or bent runs. For liquidtight flexible conduit (LFMC or LFNC), the same fill capacity rules apply, but pulling difficulty increases faster due to the corrugated interior.